VEGAVIB 63 Vibrating level switch for solids with vibrating rod and tube extension For use as overfill protection system or empty detector, especially in granules - Optimum rod design avoids buildup and sticking material - Easy setup without adjustment - Product-independent switching point - Easy cleaning - SIL 2 qualified - Instrument from the plics® family Approval without ATEX II 1G, 1/2G, 2G EEx ia IIC T6 Version / Process temperature Standard / -50...150°C With adapter / -50...250°C Detection of solids in water / -50...150°C Process fitting / Material Thread G1A PN16 / 316L Thread 1NPT PN16 / 316L Thread G1½A PN16 / 316L Thread 1½NPT PN16 / 316L Electronics Contactless electronic switch 20...253VAC/DC Relay (DPDT) 20...72VDC/20...253VAC(5A) Transistor (NPN/PNP) 10...55VDC Two-wire 8/16 mA 10...36VDC NAMUR signal Housing / Protection Plastic / IP66/IP67 Aluminium / IP66/IP68 (0,2bar) StSt electropolished 316L / IP66/IP68 (0,2bar) Cable entry / Plug connection M20x1,5 / without ½NPT / without