Separator type KFD0-CS-Ex1.51P |
|
|
Ex separator in two-wire technology for 4 … 20 mA sensors For galvanic separation between intrinsically safe and non-intrinsically safe circuits

| All advantages in an overview |
- for intrinsically safe power supply as well as for signal transmission of Ex-approved sensors in hazardous areas in conjunction with signal conditioning instruments without own Ex approval - no additional power supply required, loop-powered - transmission range 4 … 20mA |
| Mounting |
on carrier rail 35 x 7.5 acc. to EN 50022 or on carrier rail 32 acc. to EN 50035 |
|
| Operating voltage |
with > 24V voltage field circuit > 15V |
|
| Approval |
ATEX II (1) GD [EEx ia] IIC |
|
|
|