Netherlands

Change country
Imprint Search Sitemap Contact
Home » Products » Nuclear » Density Measurement
Compact Density Gauge
Principles of Operation

Density Measurement

<SPAN class=headline colspan=Density Measurement" border="0">
Nucleonic Density Gauge
Nucleonic Density gauges send a focused beam of radiation from the source holder to a detector mounted on the opposite side of the process pipe or vessel.

As the density within the pipe increases, the energy reaching the detector progressively decreases and therefore process density can be calculated.

The integral HART® transmitter in the detector is pre-programmed with a density linearisation curve. Therefore it can be commissioned easily with single-point or two-point calibration.

The optional flow meter input enables the density gauge to calculate the mass flow in pipes with diameters from 50 mm to 1000 mm.


All advantages in an overview
- integral HART® transmitter with 4 to 20 mA
  output from the head
- Non-intrusive technique is ideal for abrasive
  slurries, corrosive chemicals and toxic products
- Flow input for mass flow calculation
- Temperature compensated density
  (with RTD or 4 to 20 mA input)
- Accuracy better than ±1% of span